pipe length, including the equivalent length of fittings
D
pipe inside diameter
ρ
fluid density
v
mean velocity
ε
pipe wall roughness
Δz
rise from inlet to outlet
The calculator finds the velocity and Reynolds number, chooses the friction factor and applies the Darcy-Weisbach equation to the straight pipe. Laminar flow uses 64/Re. Turbulent flow solves the Colebrook equation by iteration.
Fittings are added by the equivalent-length method: each fitting counts as a number of pipe diameters of extra straight pipe. The values used are 30 diameters for a 90° standard elbow, 16 for a 45° elbow, 60 for a tee with flow through the branch, 8 for an open gate valve, 340 for an open globe valve and 100 for a swing check valve.
A rise from inlet to outlet adds ρ · g · Δz and a fall subtracts it. The total is straight-pipe friction plus fittings plus elevation.
Before you rely on it
Check the cold-start case. In laminar flow the pressure drop is proportional to viscosity, and oil can be many times more viscous at start-up than at operating temperature.
Between Reynolds numbers of 2,300 and 4,000 the friction factor is an interpolation. Treat results in that range as approximate.
Equivalent lengths are typical published values for standard, fully open fittings. A manufacturer's figure for the actual component is better, and fitting losses in laminar flow are estimates.
Filters, coolers, control valves and orifices are not included. Add their pressure drops separately.
Roughness values are for new, clean pipe.
Worked example
The built-in example in each unit system, so you can check a hand calculation against the calculator. Reset example loads the same inputs.
US customary units
Pipe size
NPS 2 Sch 40 (52.5 mm, 2.067 in)
Pipe material
Commercial carbon steel (0.046 mm)
Flow rate
40 gpm
Straight pipe length
100 ft
Kinematic viscosity
32 cSt
Density
54.3 lb/ft³
Elevation rise
0 ft
90° standard elbows
4
Total pressure drop
2.01 psi
Straight pipe friction
1.665 psi
Fittings
0.3442 psi
Elevation
0 psi
Velocity
3.825 ft/s
Reynolds number
1,913
Flow regime
Laminar
Darcy friction factor
0.03346
Equivalent length
120.7 ft
SI metric units
Pipe size
NPS 2 Sch 40 (52.5 mm, 2.067 in)
Pipe material
Commercial carbon steel (0.046 mm)
Flow rate
150 L/min
Straight pipe length
30 m
Kinematic viscosity
32 cSt
Density
870 kg/m³
Elevation rise
0 m
90° standard elbows
4
Total pressure drop
0.1355 bar
Straight pipe friction
0.112 bar
Fittings
0.02352 bar
Elevation
0 bar
Velocity
1.155 m/s
Reynolds number
1,895
Flow regime
Laminar
Darcy friction factor
0.03378
Equivalent length
36.3 m
Questions about this calculator
01Should I use Darcy-Weisbach or Hazen-Williams?
Hazen-Williams is an empirical formula for water in turbulent flow. Darcy-Weisbach works for any Newtonian liquid in any flow regime, which makes it the right choice for oil.
02Why did the pressure drop jump when I lowered the temperature?
Colder oil is more viscous. In laminar flow the pressure drop scales directly with viscosity, so doubling the viscosity doubles the loss. Use the viscosity-temperature calculator to find the cold viscosity, then run this one again.
03How do I add a component that is not in the fittings list?
If the manufacturer gives an equivalent length in pipe diameters, multiply it by the pipe inside diameter and add the result to the straight length. Otherwise calculate that component's pressure drop on its own and add it to the total.
The formula on this page is tested against published reference values or a written-out hand calculation. The result supports preliminary engineering and field checks. It does not replace detailed engineering analysis, the applicable project standards or professional judgment.
Start a Conversation